HIGH & LOW PRESSURE CO2 FIRE EXTINGUISHING SYSTEM

Design Integrate System

DESIGN PROVIDES ACCORDING TO THE STANDARD NFPA12, ISO, SOLAS, FSS CODE, IMO CIRCULARS & SINGAPORE STANDARD.

This standard contains requirements for carbon dioxide fire-extinguishing systems to help ensure that such equipment will function as intended throughout its life. It is intended for those, design, install, test, inspect, approve, list, operate, or maintain these systems.

Maintenance, testing and Inspection of Fire Protection System and Appliance 

Maintenance, testing and inspections shall be carried out based on the guidelines developed by the Organization (Refer to MSC.1/Circ.1432 as amended, including the amendments by MSC.1/Circ.1516)  and in a manner having due regard to ensuring the reliability of fire-fighting systems and appliances (FFE & LSA)

Table-1   Overview of maintenance, testing and inspections of main fire-fighting systems based on MSC.1/Circ.1432 and MSC.1/Circ.1516 as amended, as well as other relevant guidelines and instructions from different flag state Administrations.

HP CO2 Fire Extinguisher System Monthly Verification of each Part, etc. MSC.1/Circ.1318, 
  Annually Visual Inspection, etc. MSC.1/Circ.1318, 
 

 2 -Yearly

(Passenger Ships)

Verification of contents, etc.

Full functional test of pilot line

MSC.1/Circ.1318,

MSC.1/Circ.1318,    

 

 2.5 -Yearly

(Cargo Ships)

Verification of contents, etc.

MSC.1/Circ.1318,

SI II-2/14.2.2 item 3.11.1.1 a3   

  5 - Yearly Operation test. etc. MSC.1/Circ.1318, 
  10 -Yearly Hydrostatic test etc MSC.1/Circ.1318,